|
Control of Indicating Panels
Fire Alarm Systems -- Types of Fire Alarm Systems -- System Design -- Control of Indicating Panels -- Detector Heads -- Manual Call Points -- Alarm Sounders -- Power Units -- Diversion Relays -- Self Contained Fire Alarms -- Wiring & Installation -- Inspection & Servicing -- Statutory Regulations Control and indicating equipment performs three principal functions, namely:
Panels are fully specified in British Standards. This requires that circuits are monitored continuously and that both audible and visual indication is provided for fault and fire alarm conditions. Further requirements include that alarm sounders may only be silenced manually, after which the control panel must provide audible and visual signals until the system is reset. Silencing of alarm sounders must not prevent the alarm being raised in other zones. It should be noted that the standards require all fault/alarm indicator lamps to be in duplicate or a single lamp with audible signal of lamp failure. Control and indicating panels may include facilities for operation of ancillary services such as fixed fire extinguishing, door closing etc. The equipment should normally be sited in an area of low fire risk and on the ground floor by the entrance used by the Fire and Rescue Service and preferably viewable from outside of the building. It should be located in an area common to all building users and where automatic detection is in use, the Control Panel should be in a protected area. An alarm sounder should be sited next to the Control Unit, but not too near the telephone position. A suitable zone chart of the building should normally be installed adjacent to the Control Panel. Points to consider
|
![]() ![]() Copyright ©2011 Saint Davids Fire. All Rights Reserved. |